Frequently asked questions
Is there an additional product cost when moving from mk3 to mk4?
No. Modumax mk4 is available at the same list price as mk3. Any project-specific accessories, conversion kits or installation requirements should be considered separately.
Does mk4 reduce installation time?
Modumax mk4 is simpler to install, particularly for refurbishment projects and where reduced flue height is beneficial. The exact installation time will depend on the individual project, so avoid quoting a fixed time saving.
What is the benefit of the reduced flue height?
On two- and three-stack boilers, the flue height is approximately 240mm lower. This provides greater flexibility where plantroom or ceiling height is restricted.
Will the existing pipework or plantroom layout need to change?
For an mk3 replacement, having the same connection positions will minimise changes to existing pipework and avoid unnecessary redesign. Project-specific requirements should always be checked against the approved technical documentation.
Can Modumax mk4 replace an existing mk3?
Yes. Modumax mk4 has the same footprint and connection positions as mk3, helping make replacement within an existing Modumax plantroom straightforward.
Has performance changed?
No. Modumax mk4 has the same outputs, efficiency and core performance as mk3.
What has stayed the same?
Modumax mk4 carries forward the core Modumax proposition, including modular design, outputs and performance, familiar controls, footprint and connection positions. It is also available at the same list price as mk3.
What's new compared with mk3?
The main changes are a 7-inch touchscreen HMI, a new HMI status bar, reduced flue height on two- and three-stack boilers, a Modbus connectivity kit, VFC remote signalling supplied as standard, updated styling and an LPG conversion option.
Will the Wessex ModuMax mk3 be easy to get into the plantroom?
Yes, each module is delivered fully assembled and even the largest 762kW model will pass through a standard doorway.
For sites that are more difficult such as basement and rooftops, the modules can be separated and rebuilt when in position.
Take a look at this case study of the Langham Hotel where the boilers were separated and carried up to the rooftop plantroom.
Can the Wessex ModuMax boiler run on an open vented system?
Yes. The Wessex ModuMax boiler is able to operate on an open vented heating system.
We would advise compliance with minimum pressure requirements at boiler, reference guidance note INDG436 (Health and Safety Executive).
Open vent and cold feed pipes must be installed correctly and in compliance with BS6644. You can refer to the installer guide for detailed information on Open Vent and Cold Feed pipes.
However, Hamworthy recommends the use of sealed heating systems, where possible.
If you want to know the difference between a sealed system and open vented system, find out more here.
What is the maximum working pressure of the Wessex range?
The maximum pressure rating of the Wessex is 10bar.
This pressure is the maximum pressure that the boiler can be subjected to, or in effect the maximum lift pressure rating of the boiler safety valve.
So to allow for a pressure buffer range of 0.7-0.8bar the maximum "working pressure" would be 9.2-9.3bar.