Hamworthy Heating

Halstock stainless steel calorifier

  • Stainless steel single coil and twin coil calorifiers for indirect hot water.
  • 5 unvented calorifier models and 4 open-vented calorifiers available with continuous outputs (@44°C ∆T) of 390, 527, 1,843 and 2,106 l/h.
  • Hamworthy Web Icons JBs base set BLUE-55
  • Hamworthy Web Icons JBs base set BLUE-06
Halstock-stainless-steel-calorifier-500-DSC7436-web
Halstock-stainless-steel-calorifier-cut-away-web
Halstock-stainless-steel-calorifier-group-DSC7459-web
Halstock-calorifier-dimensions-850x400

Product information

  • Power outputs 20-108kW and storage capacities 305-965 litres

  • Indirect method of producing safe and hygienic domestic hot water (want to understand the difference between Indirect vs Direct Hot Water Systems?)

  • Fast recovery for constant hot water – as little as 13 minutes (Recovery times for 70% of the cylinder volume to 50°C 13-22 minutes)

  • Hot water cylinder and coil made out of corrosion resistant stainless steel for a long life backed up by a 5 year cylinder warranty

  • Now available with twin coils for flexibility and high performance hot water (models 500-965 only)

  • Can be integrated with solar thermal for a renewable energy option

  • Minimal heat loss for maximum economy thanks to layer of CFC-free polyurethane tank insulation under protective plastisol cladding

  • Highly efficient heat transfer from a corrugated coil design

  • Low maintenance as no sacrificial anodes or powered corrosion protection systems needed

  • Can be located wherever convenient

  • Versatility in use – coupled to Hamworthy commercial boilers or backup via immersion heater

  • UK manufactured hot water calorifiers

  • Compliant with Energy Labelling requirements of ErP

  • Available for next day delivery (dependent on stock availability, charges apply, order cut-off 12pm).

Ideal uses/applications

  • To provide domestic hot water for any type of commercial building.

  • Designed for use with natural gas, LPG or oil-fired commercial boilers for primary heat source.

  • Direct heating via optional Incoloy 800 electrical immersion heaters.

  • Suited to all areas of the UK, particularly locations with soft water (read here why).

Optional extras

  • Electric immersion heater kits

  • Top-to-bottom re-circulation/de-stratification kit to prevent stratification and protect against legionella within the water heater (factory fitted – please specify at time of ordering)

  • Choose from a wide range of service contracts to help maintain optimum performance.

  • Water

    Units

    HS305

    HS400

    HS5002CO

    HS8102CO

    HS9652CO

    Capacity, nominal

    litres

    305

    400

    500

    810

    965

    Capacity with coil

    litres

    298

    396

    496

    803

    958

    Continuous output @44°C ΔT

    l/h

    390

    527

    1843

    1843

    2106

    Continuous output @50°C ΔT

    l/h

    344

    464

    1622

    1622

    1853

    Maximum working pressure, tank

    bar

    6

    6

    6

    6

    6

    Hydraulic test pressure

    bar

    9

    9

    9

    9

    9

  • Energy

    Units

    HS305

    HS400

    HS5002CO

    HS8102CO

    HS9652CO

    Number of coils

    1

    1

    2

    2

    2

    Lower coil output

    kW

    20

    27

    67.5

    67.5

    81

    Heat up time @50°C ΔT,lower coil only

    min

    54

    53

    26

    42

    42

    Upper coil output

    kW

    N/A

    N/A

    27

    27

    27

    Heat up time @50°C ΔT,top coil only

    min

    N/A

    N/A

    66

    105

    126

    Heat up time @50°C ΔT,combined coils

    min

    N/A

    N/A

    19

    31

    31

    Recovery time 70% @50°C ΔT, combined coils

    min

    38

    36

    13

    21

    22

    10 min peak output @50°C ΔT

    litres

    361

    481

    770

    1080

    1274

    Coil max operating temperature

    °C

    100

    100

    100

    100

    100

    Coil max operating pressure

    bar

    3

    3

    3

    3

    3

    Upper coil tube diameter

    DN

    NA

    NA

    DN25

    DN25

    DN25

    Upper coil surface area

    m2

    NA

    NA

    1

    1

    1

    Lower coil tube diameter

    DN

    DN20

    DN25

    DN25

    DN25

    DN25

    Lower coil surface area

    m2

    0.75

    1

    2.5

    2.5

    3

    Reheat total delta T 50degC lower

    mins

    38

    36

    18

    29

    29

    Reheat total delta T 50degC both

    mins

    N/A

    N/A

    13

    21

    22

    Standby losses

    kW/24hr

    1.77

    2.35

    2.74

    3.29

    3.43

    ErP efficiency rating

    -

    C

    C

    C

    Compliant

    Compliant

  • Immersion

    Units

    HS305

    HS400

    HS5002CO

    HS8102CO

    HS9652CO

    Immersion heater option, power

    kW

    3

    6

    6

    9

    12

    Immersion heater option, phase

    ph

    1ph

    3ph/1ph

    3ph/1ph

    3ph

    3ph

    Heat up time, Immersion only

    hour

    5.8

    3.9

    4.9

    5.3

    4.7

    Recovery time, Immersion only

    hour

    4.1

    2.7

    3.4

    3.7

    3.3

  • Misc

    Units

    HS305

    HS400

    HS5002CO

    HS8102CO

    HS9652CO

    Expansion vessel size

    litres

    24

    35

    35

    50

    80

    Weight empty

    kg

    75

    105

    115

    140

    180

    Weight full

    kg

    379

    505

    615

    950

    1145

Partnerships

CIBSE Patron WhiteSoPHE Logo
BESA logo
ICOM

Hamworthy Heating 2025. All Rights Reserved

  • Youtube