Hamworthy Heating

Purewell Variheat mk2 condensing cast iron boiler

  • Available in 5 condensing models with outputs (@50/30°C) of 70, 95, 110, 140 and 180 kW.
  • The only cast iron condensing commercial boiler that is compliant with the Energy related Products Directive (ErP) available in the UK.
  • Hamworthy Web Icons JBs base set BLUE Product-icon-efficiency-96
  • Hamworthy Web Icons JBs base set BLUE-03
  • Hamworthy Web Icons JBs base set BLUE-33
  • Hamworthy Web Icons JBs base set BLUE-47
  • Hamworthy Web Icons JBs base set BLUE-07
  • Hamworthy Web Icons JBs base set BLUE-06
Variheat mk2 cast iron boiler
3D Purewell Variheat mk2

Product information

  • Proven reliability with a 10-year heat exchanger warranty

  • The only cast iron condensing commercial boiler that is compliant with the Energy related Products Directive (ErP) available in the UK.

  • Built in boiler sequence controls capable of controlling up to 16 boiler modules and hot water circuits

  • Easy access for servicing with quick to remove front cover hooks

  • Full spark ignitor enables servicing without the need to remove the whole burner

  • Low NOx performance (<40mg/kWh, European Class 6)

  • Non complicated design means the Purewell Variheat mk2 is easy to operate & maintain, saving on time and money

  • Highly efficient offering up to 96% gross seasonal efficiency, reducing carbon emissions and saving the end user money on fuel bills

  • Sits on same footprint as many traditional and atmospheric cast iron boilers reducing space concerns

  • Easy access to plant room as the Purewell Variheat mk2 fits through a standard doorway

  • Can be disassembled for plant rooms with difficult access

  • Tolerant of existing heating systems making the Purewell Variheat mk2 the perfect choice when replacing old atmospheric boilers

  • Operates in sealed and open vented heating systems (you can read about the differences of Sealed 'v' Open Vented heating systems here)

  • Suitable for use with LPG Air for installation in the Channel Islands

  • BIM objects available to assist in design and management

Ideal uses/applications

Optional extras

Reverse return header kit available for:

  • 2 boiler installation

  • 3 boiler installation

  • 4 boiler installation ( 2 x 2 boiler installation kit)

  • Flues available

  • Choose from a wide range of service contracts to help maintain optimum performance.

  • Book commissioning at the same time as placing your order for improved warranty terms.

  • Energy

    Units

    PV70c

    PV95c

    PV110c

    PV140c

    PV180c

    Building regulations - seasonal efficiency

    (%) gross

    95.3

    95.6

    95.8

    95.7

    94.6

    ErP efficiency rating (modules ≤ 70 kW only)

    A

    N/A

    N/A

    N/A

    N/A

    Boiler output (non-condensing) mean 70°C - max

    kW

    63.5

    86.3

    99.8

    134.4

    172.8

    Boiler output (non-condensing) mean 70°C - min

    kW

    21.2

    28.8

    33.3

    44.8

    50.3

    Boiler output (condensing) mean 40°C - max

    kW

    70

    95

    110

    140

    180

    Boiler output (condensing) mean 40°C - min

    kW

    23.3

    31.67

    36.37

    46.67

    53.0

    Gross boiler input - max

    kW

    72.2

    98.4

    115

    151.3

    194.6

    Gross boiler input - min

    kW

    24.1

    26.7

    38.3

    50.4

    56.6

    Net boiler input - max

    kW

    65

    88.6

    103.5

    136.3

    175.2

    Net boiler input - min

    kW

    21.7

    29.6

    34.5

    45.4

    51.0

  • Water

    Units

    PV70c

    PV95c

    PV110c

    PV140c

    PV180c

    Water content

    litres

    8

    8

    8

    11

    11

    System design flow rate @ 20°C ∆T rise

    l/s

    0.8

    1.1

    1.3

    1.7

    2.1

    Water side pressure loss @ 20°C ∆T rise

    mbar

    32

    52

    72

    134

    221

    System design flow rate @ 11°C ∆T rise

    l/s

    1.5

    2.1

    2.4

    3

    3.9

    Water side pressure loss @ 11°C ∆T rise

    mbar

    96

    176

    244

    442

    731

    Maximum water pressure

    bar g

    6

    6

    6

    6

    6

  • Gas

    Units

    PV70c

    PV95c

    PV110c

    PV140c

    PV180c

    Gas flow rate natural gas (G20) - max

    m3/hr

    6.9

    9.4

    10.9

    14.4

    18.5

    Nominal inlet pressure natural gas (G20) - max

    mbar

    20

    20

    20

    20

    20

    Maximum gas inlet pressure natural gas (G20)

    mbar

    25

    25

    25

    25

    25

  • Flue

    Units

    PV70c

    PV95c

    PV110c

    PV140c

    PV180c

    Flue Gas Flow Rate@ 15°C, 9.5% CO2

    m3/hr

    86

    117

    137

    180

    232

    Approx. flue gas temperature @ 50/30°C

    °C

    40

    40

    45

    50

    50

    Approx. flue gas temperature @ 80/60°C

    °C

    60

    60

    65

    70

    75

    Pressure at boiler flue spigot @full load

    Pa

    100

    100

    100

    100

    100

    Dry NOx emission*

    mg/kWh

    21.3

    31.1

    39.1

    32

    37.8

  • Connection

    Units

    PV70c

    PV95c

    PV110c

    PV140c

    PV180c

    Water flow/return connections

    inches

    R2”

    R2”

    R2”

    R2”

    R2”

    Gas inlet connection pipe thread size

    inches

    R1”

    R1”

    R1”

    R1”

    R1”

    Nominal flue diameter (I/D)

    mm

    150

    150

    150

    150

    150

  • Electrics

    Units

    PV70c

    PV95c

    PV110c

    PV140c

    PV180c

    Electrical supply

    230 V 1 Ph 50 Hz

    230 V 1 Ph 50 Hz

    230 V 1 Ph 50 Hz

    230 V 1 Ph 50 Hz

    230 V 1 Ph 50 Hz

    Power consumption @ max

    W

    94

    94

    94

    207

    207

    IEC power outlet power consumption @ max

    W

    460

    460

    460

    460

    460

    Start current and run current

    Amp

    0.54

    0.54

    0.54

    0.6

    0.6

    Approx shipping weight

    kg

    195

    195

    195

    250

    250

    Noise emission @1 m and @maximum boiler modulation

    Max dB (A)

    53

    53

    53

    65

    65

    CO2 (±0.25%) - max

    %

    9.5

    9.5

    9.5

    9.5

    9.5

    CO2 (±0.25%) - min

    %

    9.5

    9.5

    9.5

    8.5

    8.5