Hamworthy Heating

Dorchester DR-FC Evo condensing water heater

  • Fully automatic, condensing direct fired water heater for domestic hot water.
  • 7 models available with continuous outputs (@44°C ∆T) of 600, 630, 970, 1200, 1700, 2000 & 2400 l/h.
  • Hamworthy Web Icons JBs base set BLUE Product-icon-efficiency-98
  • Hamworthy Web Icons JBs base set BLUE-04
  • Hamworthy Web Icons JBs base set BLUE-20
  • Hamworthy Web Icons JBs base set BLUE-06
  • Hamworthy Web Icons JBs base set BLUE-07
Dorchester-DR-FC-Evo-water-heater-web
Dorchester-DR-FC-evo-drawing
Dorchester-DR-FC-Evo-water-heater-plant-room-pembroke-house-web
abbey-hill-academy-dorchester-dr-fc-evo-water-heater

Product information

  • Power outputs 30-119kW and storage capacities of 227-504 litres.

  • Safe and clean domestic hot water generation.

  • Reduces energy use and running costs by maximising condensing water heater performance.

  • Meets the strict standards for efficiencies and NOx emissions in new buildings.

  • Ultra-quiet operation means it can be installed close to point of use without disturbance to occupants.

  • Closely matches hot water demand, reducing wastage.

  • Down firing pre-mix modulating burner reduces the risk of scale build up impacting on the heat transfer.

  • Large range of time and temperature control features built in as standard.

  • Electronic Anode fitted as standard.

  • Natural gas and lpg water heater options.

  • Easy access for service and maintenance.

  • Full project assistance available from our dedicated hot water expert to help with hot water sizing and selection of equipment to match the application.

  • Extensive back up and support from our team of experienced engineers across the UK.

  • Long term commitment to spare parts.

  • Water heater BIM objects available to assist in project design and management

  • Available for next day delivery (dependent on stock availability, charges apply, order cut-off 12pm).

Ideal uses/applications

Optional extras

  • Unvented water supply kit - essential for any unvented application and includes an expansion vessel sized for the water heater and local pipework only.

  • Top to bottom pump recirculation pump kit to prevent stratification and protect against legionella within the water heater.

  • Remote monitoring unit.

  • Room Sealed Flue Systems:

    • Concentric flue systems type C13–Horizontal termination.

    • Concentric flue systems type C33–Vertical termination.

    • Twin duct flue systems type C53–Vertical flue termination with Horizontal air inlet.

  • Conventional Open Flue Systems:

    • Open flue systems type B23–Vertical termination.

  • Choose from a wide range of service contracts to help maintain optimum performance.

  • Ensure your new Hamworthy products are set to our recommendations and benefit from improved warranty terms with a commissioning package.

  • Energy

    Units

    DR-FC Evo 25

    DR-FC Evo 30

    DR-FC Evo 45

    DR-FC Evo 60

    DR-FC Evo 80

    DR-FC Evo 95

    DR-FC Evo 120

    Building Regulations thermal efficiency gross

    %

    96

    98

    96

    95

    97

    95

    95

    ErP efficiency rating (modules ≤ 70 kW only)

    -

    A

    A

    A

    A

    N/A

    N/A

    N/A

    Heating-up time, ΔT = 44°C

    min.

    23

    37

    24

    20

    19

    16

    13

    Heating-up time, ΔT = 50°C

    min.

    26

    42

    27

    23

    21

    18

    15

    Heating-up time, ΔT = 55°C

    min.

    29

    46

    30

    25

    23

    20

    16

    Standby losses

    kW/24h

    4.2

    4.7

    4.7

    4.7

    6.7

    6.7

    6.7

  • Water

    Units

    DR-FC Evo 25

    DR-FC Evo 30

    DR-FC Evo 45

    DR-FC Evo 60

    DR-FC Evo 80

    DR-FC Evo 95

    DR-FC Evo 120

    Continuous output with 44°C ΔT

    l/h

    600

    630

    790

    1200

    1700

    2000

    2400

    1st hour output with 44°C ΔT

    l

    730

    870

    1300

    1500

    1900

    2200

    2600

    Continuous output with 50°C ΔT

    l/h

    530

    560

    850

    1100

    1500

    1700

    2100

    1st hour output with 50°C ΔT

    l

    630

    730

    1100

    1300

    1700

    1900

    2300

    Continuous output with 55°C ΔT

    l/h

    480

    510

    780

    930

    1300

    1600

    1900

    1st hour output with 55°C ΔT

    l

    560

    640

    930

    1100

    1500

    1700

    2000

    Storage capacity

    litres

    227

    386

    386

    386

    504

    504

    504

    Maximum operating water pressure (open vented)

    bar

    8

    8

    8

    8

    8

    8

    8

    Maximum operating water pressure (unvented)

    bar

    5.3

    5.3

    5.3

    5.3

    5.3

    5.3

    5.3

    Expansion relief valve setting (unvented kit)

    bar

    6

    6

    6

    6

    6

    6

    6

    ErP load profile

    -

    XXL

    XXL

    XXL

    XXL

    3XL

    3XL

    3XL

  • Nat Gas

    Units

    DR-FC Evo 25

    DR-FC Evo 30

    DR-FC Evo 45

    DR-FC Evo 60

    DR-FC Evo 80

    DR-FC Evo 95

    DR-FC Evo 120

    Input, gross – maximum

    kW

    31.6

    32.6

    51.2

    62.1

    85

    103.4

    126.3

    Output – maximum

    kW

    30.5

    32

    49.3

    59.3

    82.6

    98.7

    119.4

    Gas inlet pressure – nominal

    mbar

    20

    20

    20

    20

    20

    20

    20

    Gas flow rate – maximum @1013.25 mbar and 15°C

    m3/h

    3.1

    3.2

    5

    6

    8.3

    10.1

    12.3

  • LPG

    Units

    DR-FC Evo 25

    DR-FC Evo 30

    DR-FC Evo 45

    DR-FC Evo 60

    DR-FC Evo 80

    DR-FC Evo 95

    DR-FC Evo 120

    Input, gross – maximum

    kW

    31

    32

    50.1

    60.8

    83.2

    101.2

    123.6

    Output – maximum

    kW

    30.5

    32

    49.3

    59.3

    82.6

    98.7

    119.4

    Gas inlet pressure – nominal

    mbar

    37

    37

    37

    37

    37

    37

    37

    Gas flow rate – [email protected] mbar and 15°C

    kg/h

    2.3

    2.3

    3.7

    4.4

    6.1

    7.4

    9

  • Flue

    Units

    DR-FC Evo 25

    DR-FC Evo 30

    DR-FC Evo 45

    DR-FC Evo 60

    DR-FC Evo 80

    DR-FC Evo 95

    DR-FC Evo 120

    Approximate flue gas volume @15°C, 9.8% CO2, N.T.P. (Nat. Gas - G20)

    kg/h

    51.7

    53.5

    84.6

    103.7

    141.9

    172.9

    213.3

    Flue gas temperature – maximum

    °C

    45

    50

    60

    65

    50

    55

    60

    NOx emission, dry air free,European Class 5. Maximum (at part load)

    mg/kWh

    24

    32

    36

    37

    34

    36

    37

    Pressure at the flue outlet only (B23) with zero pressure at air inlet

    Pa

    52

    62

    133

    173

    88

    126

    180

  • Electrical

    Units

    DR-FC Evo 25

    DR-FC Evo 30

    DR-FC Evo 45

    DR-FC Evo 60

    DR-FC Evo 80

    DR-FC Evo 95

    DR-FC Evo 120

    Start current–maximum (maximum power)

    A (W)

    0.59 (135)

    0.59 (135)

    0.59 (135)

    0.59 (135)

    0.61 (140)

    0.61 (140)

    0.61 (140)

    Run current–maximum (maximum power)

    A (W)

    0.2 (45)

    0.2 (45)

    0.32 (75)

    0.5 (115)

    0.41 (95)

    0.63 (145)

    1.05 (240)

    Electrical supply

    Vac

    230 V 1 PH 50 Hz

    230 V 1 PH 50 Hz

    230 V 1 PH 50 Hz

    230 V 1 PH 50 Hz

    230 V 1 PH 50 Hz

    230 V 1 PH 50 Hz

    230 V 1 PH 50 Hz

    Voltage tolerance

    % of Vac

    -15% +10%

    -15% +10%

    -15% +10%

    -15% +10%

    -15% +10%

    -15% +10%

    -15% +10%

  • Misc.

    Units

    DR-FC Evo 25

    DR-FC Evo 30

    DR-FC Evo 45

    DR-FC Evo 60

    DR-FC Evo 80

    DR-FC Evo 95

    DR-FC Evo 120

    Noise level @2m from flue terminal

    dB(A)

    <45

    <45

    <45

    <45

    <45

    <45

    <45

    Number of (power) anodes

    -

    1

    2

    2

    2

    2

    2

    2

    Weight when empty

    kg

    196

    239

    239

    239

    405

    405

    405

    Approximate shipping weight

    kg

    215

    260

    260

    260

    426

    426

    426

    Maximum floor load/ weight filled with water

    kg

    423

    625

    625

    625

    909

    909

    909

Partnerships

CIBSE Patron WhiteSoPHE Logo
BESA logo
ICOM

Hamworthy Heating 2025. All Rights Reserved

  • Youtube
  • Linkedin