Hamworthy Heating

Tyneham CO2 & CO2Q air source heat pump

  • This range can be installed flush against a wall or back to back with another unit as well as benefiting from low dB(A) rating for minimal background noise.
  • Available in 3 standard noise models (CO2) with outputs of 65, 95 and 130kW, and 3 low noise models (CO2Q) with outputs of 65, 95 and 130kW.
    Tyneham CO2 & CO2Q air source heat pump
    Tyneham CO2 commercial ASHP rh facing
    Tyneham CO2 commercial ASHP front facing
    Tyneham CO2 commercial ASHP lh facing

    Product information

    • Made in the UK

    • Ultra-low GWP due to the use of R744 natural refrigerant

    • Commercial monobloc air source heat pump

    • Single unit with the refrigeration cycle contained within the outdoor unit

    • Inverter controlled compressor to accurately match the heat demand

    • Able to achieve high temperatures up to 70°C

    • Highly efficient with co-efficient of performance (COP) rating up to 3.4

    • Quiet noise level as standard with low noise models available (CO2Q)

    • Suited to larger installations - cascade systems to achieve higher output

    • Can be installed against a wall or back to back with another unit with no installation clearances required at the rear of the unit

    • Combine with Hamworthy modular boilers for a hybrid heating system

    • 2-year warranty (extended to 5 years if commissioned by Hamworthy)

    • Back up and long-term support from our team of experienced engineers across the UK

    Terms and conditions apply * Coefficient of Performance (COP) rated at EN14825 test conditions Water 35°C/ Air 7°C **The sound power has been established in general accordance with BS EN ISO 3740: 2019 with a survey grade (sRO) = 4dB *** Sound pressure value calculated from the sound power level in condition (9) using the standard UNI EN ISO 3744:2022

    Ideal uses/applications

    • Commercial and industrial processes

    • Domestic hot water 70°C

    • Retrofit installations

    • District heating systems

    • Minimum space for outdoor unit

    • Client with net zero commitments

    • Sites requiring low GWP

    • New build - heating & DHW

    Optional extras

    • Master controller

    • DHW controller

    • Flexible hoses

    • Burst disc pressure relief kit

    • Exogel antifreeze kit

    • Anti-corrosion coating for installations close to the sea (special order)

    • Energy

      Energy

      Units

      65kW

      65kW - Q

      95kW

      95kW - Q

      130kW

      130kW - Q

      Heat Pump Space Heating [55°C]

      ErP rating

      A+++

      A+++

      -

      -

      -

      -

      Heat Pump Space Heating [55°C]

      COP*

      3

      3

      3

      3

      3

      3

      Heat Pump Space Heating [65°C]

      ErP rating

      A+++

      A+++

      -

      -

      -

      -

      Heat Pump Space Heating [65°C]

      COP*

      3.4

      3.4

      3.4

      3.4

      3.4

      3.4

      Refrigerant

      R744

      R744

      R744

      R744

      R744

      R744

      Refrigerant Charge

      (kg)

      4.8

      4.8

      6.5

      6.5

      10

      10

      Global Warming Potential

      GWP

      1

      1

      1

      1

      1

      1

    • Heating

      Heating

      Units

      65kW

      65kW - Q

      95kW

      95kW - Q

      130kW

      130kW - Q

      Heating (A7/W65)

      Capacity (kW)

      65

      65

      95

      95

      130

      130

      Heating (A7/W65)

      Power Input (kW)

      17

      17

      25

      25

      34

      34

      Heating (A7/W65)

      SCOP

      3.5

      3.5

      3.5

      3.5

      3.5

      3.5

      Max Flow Temperature

      Max [°C]

      70

      70

      70

      70

      70

      70

      Air Temperature Range

      Min/Max [°C]

      (-15 no max)

      (-15 no max)

      (-15 no max)

      (-15 no max)

      (-15 no max)

      (-15 no max)

    • Sound

      Sound

      Units

      65kW

      65kW - Q

      95kW

      95kW - Q

      130kW

      130kW - Q

      Sound Data Outdoor unit

      Power Level dB(A)**

      74

      71

      75

      72

      75

      72

      Sound Data Outdoor unit

      Pressure Level at 10m dB (A)***

      43

      40

      44

      40

      44

      40

    • Connections

      Connections

      Units

      65kW

      65kW - Q

      95kW

      95kW - Q

      130kW

      130kW - Q

      Pipework Connection Sizes

      Heating Flow (mm)

      28

      28

      35

      35

      42

      42

      Pipework Connection Sizes

      Heating Return (mm)

      28

      28

      35

      35

      42

      42

    • Electrics

      Electrics

      Units

      65kW

      65kW - Q

      95kW

      95kW - Q

      130kW

      130kW - Q

      Electrical Supply

      (v)

      400

      400

      400

      400

      400

      400

      Phase

      Three

      Three

      Three

      Three

      Three

      Three

      Max Running Current

      (amp)

      45.07

      45.07

      67.55

      67.55

      82.19

      82.19

      Fuse Rating

      (amp)

      63

      63

      80

      80

      100

      100

    • Dimensions

      Dimensions

      Units

      65kW

      65kW - Q

      95kW

      95kW - Q

      130kW

      130kW - Q

      Width

      (mm)

      2190

      2190

      3051

      3051

      3101

      3101

      Depth

      (mm)

      1160

      1160

      1160

      1160

      1457

      1457

      Height

      (mm)

      1853

      2401

      1853

      2401

      1853

      2401

      Weight

      (kg)

      935

      1000

      1260

      1365

      1300

      1590

    Partnerships