Tyneham CO2 & CO2Q air source heat pump
- This range can be installed flush against a wall or back to back with another unit as well as benefiting from low dB(A) rating for minimal background noise.
- Available in 3 standard noise models (CO2) with outputs of 65, 95 and 130kW, and 3 low noise models (CO2Q) with outputs of 65, 95 and 130kW.
Product information
Made in the UK
Ultra-low GWP due to the use of R744 natural refrigerant
Commercial monobloc air source heat pump
Single unit with the refrigeration cycle contained within the outdoor unit
Inverter controlled compressor to accurately match the heat demand
Able to achieve high temperatures up to 70°C
Highly efficient with co-efficient of performance (COP) rating up to 3.4
Quiet noise level as standard with low noise models available (CO2Q)
Suited to larger installations - cascade systems to achieve higher output
Can be installed against a wall or back to back with another unit with no installation clearances required at the rear of the unit
Combine with Hamworthy modular boilers for a hybrid heating system
2-year warranty (extended to 5 years if commissioned by Hamworthy)
Back up and long-term support from our team of experienced engineers across the UK
Terms and conditions apply * Coefficient of Performance (COP) rated at EN14825 test conditions Water 35°C/ Air 7°C **The sound power has been established in general accordance with BS EN ISO 3740: 2019 with a survey grade (sRO) = 4dB *** Sound pressure value calculated from the sound power level in condition (9) using the standard UNI EN ISO 3744:2022
Ideal uses/applications
Commercial and industrial processes
Domestic hot water 70°C
Retrofit installations
District heating systems
Minimum space for outdoor unit
Client with net zero commitments
Sites requiring low GWP
New build - heating & DHW
Optional extras
Master controller
DHW controller
Flexible hoses
Burst disc pressure relief kit
Exogel antifreeze kit
Anti-corrosion coating for installations close to the sea (special order)
- Energy
Energy
Units
65kW
65kW - Q
95kW
95kW - Q
130kW
130kW - Q
Heat Pump Space Heating [55°C]
ErP rating
A+++
A+++
-
-
-
-
Heat Pump Space Heating [55°C]
COP*
3
3
3
3
3
3
Heat Pump Space Heating [65°C]
ErP rating
A+++
A+++
-
-
-
-
Heat Pump Space Heating [65°C]
COP*
3.4
3.4
3.4
3.4
3.4
3.4
Refrigerant
R744
R744
R744
R744
R744
R744
Refrigerant Charge
(kg)
4.8
4.8
6.5
6.5
10
10
Global Warming Potential
GWP
1
1
1
1
1
1
- Heating
Heating
Units
65kW
65kW - Q
95kW
95kW - Q
130kW
130kW - Q
Heating (A7/W65)
Capacity (kW)
65
65
95
95
130
130
Heating (A7/W65)
Power Input (kW)
17
17
25
25
34
34
Heating (A7/W65)
SCOP
3.5
3.5
3.5
3.5
3.5
3.5
Max Flow Temperature
Max [°C]
70
70
70
70
70
70
Air Temperature Range
Min/Max [°C]
(-15 no max)
(-15 no max)
(-15 no max)
(-15 no max)
(-15 no max)
(-15 no max)
- Sound
Sound
Units
65kW
65kW - Q
95kW
95kW - Q
130kW
130kW - Q
Sound Data Outdoor unit
Power Level dB(A)**
74
71
75
72
75
72
Sound Data Outdoor unit
Pressure Level at 10m dB (A)***
43
40
44
40
44
40
- Connections
Connections
Units
65kW
65kW - Q
95kW
95kW - Q
130kW
130kW - Q
Pipework Connection Sizes
Heating Flow (mm)
28
28
35
35
42
42
Pipework Connection Sizes
Heating Return (mm)
28
28
35
35
42
42
- Electrics
Electrics
Units
65kW
65kW - Q
95kW
95kW - Q
130kW
130kW - Q
Electrical Supply
(v)
400
400
400
400
400
400
Phase
Three
Three
Three
Three
Three
Three
Max Running Current
(amp)
45.07
45.07
67.55
67.55
82.19
82.19
Fuse Rating
(amp)
63
63
80
80
100
100
- Dimensions
Dimensions
Units
65kW
65kW - Q
95kW
95kW - Q
130kW
130kW - Q
Width
(mm)
2190
2190
3051
3051
3101
3101
Depth
(mm)
1160
1160
1160
1160
1457
1457
Height
(mm)
1853
2401
1853
2401
1853
2401
Weight
(kg)
935
1000
1260
1365
1300
1590