Hamworthy Heating

Dorchester DR-CC compact condensing water heater

  • Fully automatic, simple to operate condensing direct fired water heater for domestic hot water.
  • 9 models available with continuous outputs (@44°C ∆T) of 228, 233, 374, 461, 465, 602, 608 & 614 l/h.
  • Hamworthy Web Icons JBs base set BLUE Product-icon-efficiency-98
  • Hamworthy Web Icons JBs base set BLUE-04
  • Hamworthy Web Icons JBs base set BLUE-20
  • Hamworthy Web Icons JBs base set BLUE-06
  • Hamworthy Web Icons JBs base set BLUE-07
Dorchester-DR-CC-condensing-water-heater-front-web-850x400
Dorchester-DR-CC-condensing-water-heater-inside-cover-web-850x400
Dorchester-DR-CC-condensing-water-heater-side-web-850x400

Product information

  • Low power outputs 11-29kW and storage capacities of 162-384 litres.

  • Compact, standalone water heating unit for safe and clean domestic hot water generation.

  • No clearances required at the rear and minimal clearances at top and sides allow easy siting in any plant room.

  • Reduces energy use and running costs by maximising condensing water heater performance.

  • Meets the strict standards for efficiencies and NOx emissions (under 37 mg/kWh) in new buildings.

  • Load profiles of XL or XXL and an A rating ensure all models in the range are fully compliant with the ErP (Energy-related Products Directive) regulations.

  • Closely matches hot water demand, reducing wastage of energy.

  • Electronic Anode fitted as standard to protect against corrosion.

  • No top-to-bottom re-circulation kit required due to the heat exchanger coil positioned in the centre of the unit for even heat distribution and reduced likelihood of stratification.

  • Down firing pre-mix modulating burner reduces the risk of scale build up impacting on the heat transfer.

  • Natural gas and LPG water heater options.

  • All components accessible under front cover for ease of service and maintenance.

  • Flexible flue options (see optional extras tab and brochure for details).

  • Full project assistance available from our dedicated hot water expert to help with hot water sizing and selection of equipment to match the application.

  • Extensive back up and support from our team of experienced engineers across the UK.

  • Long-term commitment to spare parts.

  • BIM objects available to assist in design and management

  • Available for next day delivery (dependent on stock availability, charges apply, order cut-off 12pm).

Ideal uses/applications

Optional extras

  • Unvented water supply kit - essential for any unvented application. Includes an expansion vessel sized for the water heater and local pipework only.

  • Room Sealed Flue Systems:

    • Concentric flue systems type C13–Horizontal termination.

    • Concentric flue systems type C33–Vertical termination.

    • Concentric flue systems type C43.

  • Twin duct flue systems type C53–Vertical flue termination with Horizontal air inlet.

  • Conventional Open Flue Systems:

    • Open flue systems type B23–Vertical termination.

  • Choose from a wide range of service contracts to help maintain optimum performance of your water heater.

  • Book commissioning at the same time as placing your order for improved warranty terms.

  • Water

    Units

    DR-CC 12-160

    DR-CC 12-200

    DR-CC 20-160

    DR-CC 20-200

    DR-CC 24-245

    DR-CC 24-285

    DR-CC 32-245

    DR-CC 32-285

    DR-CC 32-380

    Continuous output with 44°C ΔT

    l/h

    228

    233

    374

    374

    461

    465

    602

    608

    614

    1st hour output with 44°C ΔT

    l

    360

    470

    510

    620

    740

    820

    870

    960

    1100

    Continuous output with 50°C ΔT

    l/h

    201

    205

    329

    329

    406

    410

    530

    535

    540

    1st hour output with 50°C ΔT

    l

    310

    410

    440

    540

    640

    720

    760

    840

    950

    Continuous output with 56°C ΔT

    l/h

    180

    183

    294

    294

    362

    366

    473

    478

    482

    1st hour output with 56°C ΔT

    l

    270

    360

    380

    480

    560

    630

    670

    740

    840

    Storage capacity

    litres

    162

    202

    162

    202

    247

    288

    247

    288

    384

    Maximum working pressure

    bar

    8

    8

    8

    8

    8

    8

    8

    8

    8

    ErP load profile

    -

    XL

    XL

    XL

    XL

    XXL

    XXL

    XXL

    XXL

    XXL

  • Energy

    Units

    DR-CC 12-160

    DR-CC 12-200

    DR-CC 20-160

    DR-CC 20-200

    DR-CC 24-245

    DR-CC 24-285

    DR-CC 32-245

    DR-CC 32-285

    DR-CC 32-380

    Building Regulations thermal efficiency gross

    %

    96

    98

    95

    95

    96

    97

    95

    96

    97

    ErP efficiency rating

    -

    A

    A

    A

    A

    A

    A

    A

    A

    A

    Heating-up time, ΔT = 44°C

    min.

    27

    41

    17

    27

    25

    31

    20

    24

    31

    Heating-up time, ΔT = 50°C

    min.

    31

    47

    19

    30

    29

    35

    22

    27

    36

    Heating-up time, ΔT = 56°C

    min.

    34

    52

    22

    34

    32

    40

    25

    31

    40

    Standby losses

    kW/24h

    2.16

    2.3

    2.16

    2.3

    2.64

    2.97

    2.64

    2.97

    2.9

  • Nat Gas

    Units

    DR-CC 12-160

    DR-CC 12-200

    DR-CC 20-160

    DR-CC 20-200

    DR-CC 24-245

    DR-CC 24-285

    DR-CC 32-245

    DR-CC 32-285

    DR-CC 32-380

    Input, gross – maximum

    kW

    12.1

    12.1

    20

    20

    24.4

    24.4

    32.2

    32.2

    32.2

    Input, net - maximum

    kW

    10.9

    10.9

    18

    18

    22

    22

    29

    29

    29

    Output – maximum

    kW

    11.7

    11.9

    19.1

    19.1

    23.5

    23.8

    30.7

    31

    31.3

    Gas inlet pressure – nominal

    mbar

    20

    20

    20

    20

    20

    20

    20

    20

    20

    Gas flow rate – maximum @1013.25 mbar and 15°C

    m3/h

    1.2

    1.2

    1.9

    1.9

    2.3

    2.3

    3.1

    3.1

    3.1

  • LPG

    Units

    DR-CC 12-160

    DR-CC 12-200

    DR-CC 20-160

    DR-CC 20-200

    DR-CC 24-245

    DR-CC 24-285

    DR-CC 32-245

    DR-CC 32-285

    DR-CC 32-380

    Input, gross – maximum

    kW

    11.8

    11.8

    19.6

    19.6

    23.9

    23.9

    31.5

    31.5

    31.5

    Output – maximum

    kW

    11.4

    11.6

    18.7

    18.7

    23

    23.3

    30.1

    30.4

    30.7

    Gas inlet pressure – nominal

    mbar

    37

    37

    37

    37

    37

    37

    37

    37

    37

    Gas flow rate – [email protected] mbar and 15°C

    kg/h

    0.8

    0.8

    1.4

    1.4

    1.7

    1.7

    2.3

    2.3

    2.3

  • Flue

    Units

    DR-CC 12-160

    DR-CC 12-200

    DR-CC 20-160

    DR-CC 20-200

    DR-CC 24-245

    DR-CC 24-285

    DR-CC 32-245

    DR-CC 32-285

    DR-CC 32-380

    Flue gas temperature – maximum

    °C

    42

    61

    42

    61

    57

    65

    57

    65

    65

    NOx emission, dry air free*

    mg/kWh

    22

    22

    30

    30

    33

    33

    37

    37

    37

    Pressure at the flue outlet only (B23)**

    Pa

    33

    33

    59

    59

    108

    108

    192

    192

    192

  • Electrical

    Units

    DR-CC 12-160

    DR-CC 12-200

    DR-CC 20-160

    DR-CC 20-200

    DR-CC 24-245

    DR-CC 24-285

    DR-CC 32-245

    DR-CC 32-285

    DR-CC 32-380

    Start current–maximum (maximum power)

    A (W)

    25

    25

    36

    36

    51

    51

    85

    85

    85

    Run current–maximum (maximum power)

    A (W)

    85

    85

    85

    85

    105

    105

    105

    105

    105

    Electrical supply

    Vac

    230V 50Hz

    230V 50Hz

    230V 50Hz

    230V 50Hz

    230V 50Hz

    230V 50Hz

    230V 50Hz

    230V 50Hz

    230V 50Hz

    Voltage tolerance

    % of Vac

    -15% +10%

    -15% +10%

    -15% +10%

    -15% +10%

    -15% +10%

    -15% +10%

    -15% +10%

    -15% +10%

    -15% +10%

  • Misc.

    Units

    DR-CC 12-160

    DR-CC 12-200

    DR-CC 20-160

    DR-CC 20-200

    DR-CC 24-245

    DR-CC 24-285

    DR-CC 32-245

    DR-CC 32-285

    DR-CC 32-380

    Noise level

    dB(A)

    41

    41

    52

    52

    53

    53

    58

    58

    58

    Number of anodes

    -

    1

    1

    1

    1

    2

    2

    2

    2

    2

    Weight when empty

    kg

    95

    106

    95

    106

    120

    136

    120

    136

    155

    Approximate shipping weight

    kg

    114

    122

    114

    122

    136

    153

    136

    153

    172

    Maximum floor load/ weight filled with water

    kg

    255

    306

    255

    306

    365

    429

    365

    429

    551

    *European Class 6. Max (at part load) **with zero pressure at air inlet