Arne flue gas economiser
- Flue gas economiser for use with non condensing power flame boilers.
- Available in 18 models to be used with both individual and multiple boiler applications.
Product information
Saves money and increases boiler efficiency by re-using heat from the boiler flue gases.
Versatile design gives the Arne the ability to be used in both new and existing commercial boiler installations.
Manufactured with high quality stainless steel tubes, providing less resistance and higher tolerance of flue gas condensate.
There are 14 models available in the standard Arne Eco range suitable for boiler outputs from 130kW to 5630kW.
There are 4 models of the Arne Eco Turbo available. These economisers are designed for multiple boiler installations with outputs from 400kW to 1430kW.
Choice of flue connection to the side or rear of the economiser.
Especially suited for installation with floor standing sectional or steel shell power flame boilers such as Hamworthy’s Ensbury LT and Melbury HE.
Ideal uses/applications
Recover heat from flue gases of a non-condensing boiler to increase efficiency by up to 18%.
Optional extras
There are no optional extras for this product.
- Technical data
Units
1 or 1 dual
2 or 2 dual
3 or 3 dual
4 or 4 dual
7 or 7 dual
10 or 10 dual
14 or 14 dual
18 or 18 dual
24 or 24 dual
32 or 32 dual
42 or 42 dual
56 or 56 dual
Model name
AE 130
AE 200
AE 300
AE 465
AE 710
AE 1080
AE 1430
AE 1870
AE 2440
AE 3230
AE 4260
AE 5630
Minimum Output
kW
95
150
230
350
540
815
1240
1630
2150
2800
3700
4900
Maximum Output
kW
170
260
400
620
940
1430
1630
2150
2800
3700
4900
6470
Output
kW
130
200
300
465
710
1080
1430
1870
2440
3230
4260
5630
Single-Pass gas circuit resistance
mbar
0.3
0.3
0.3
1.7
1.7
1.7
1.7
1.7
1.7
1.8
1.8
1.8
Double-Pass gas circuit resistance
mbar
0.4
0.4
0.4
2.1
2.1
2.4
2.4
2.4
2.5
2.5
2.5
2.6
First Pass water circuit resistance
Flow rate in l/sec
1.80
2.78
5.17
5.56
8.33
12.56
14.44
16.39
18.33
21.94
25.83
33.33
First Pass water circuit resistance
mbar
25
50
100
75
140
160
170
175
180
182
187
187
Second Pass water circuit resistance
Flow rate in l/sec
0.94
0.94
0.94
0.94
0.94
1.89
3.78
3.78
3.78
3.78
3.78
3.78
Second Pass water circuit resistance
mbar
300
300
300
300
300
300
170
250
230
280
360
470
Minimum boiler output
kW
95
150
230
350
540
815
1240
1630
2150
2800
3700
4900
Maximum boiler output
kW
170
260
400
620
940
1430
1630
2150
2800
3700
4900
6470
Weight when empty - single pass type
kg
135
160
190
205
250
335
396
510
660
825
1015
1250
Weight when empty - dual pass type
kg
175
205
243
250
304
455
535
680
870
1100
1350
1675
Water volume first pass
l
22
27
34
40
51
86
107
130
163
227
290
375
Water volume second pass
l
4
6
8.5
6
9
28
36
46
60
78
103
135