Hamworthy Heating

Purewell Variheat mk2 condensing cast iron boiler

  • Available in 5 condensing models with outputs (@50/30°C) of 70, 95, 110, 140 and 180 kW.
  • The only cast iron condensing commercial boiler that is compliant with the Energy related Products Directive (ErP) available in the UK.
  • Hamworthy Web Icons JBs base set BLUE Product-icon-efficiency-96
  • Hamworthy Web Icons JBs base set BLUE-03
  • Hamworthy Web Icons JBs base set BLUE-33
  • Hamworthy Web Icons JBs base set BLUE-47
  • Hamworthy Web Icons JBs base set BLUE-07
  • Hamworthy Web Icons JBs base set BLUE-06
Variheat mk2 cast iron boiler
3D Purewell Variheat mk2
Cast iron reliability

Product information

  • Proven reliability with a 10-year heat exchanger warranty

  • The only cast iron condensing commercial boiler that is compliant with the Energy related Products Directive (ErP) available in the UK.

  • Built in boiler sequence controls capable of controlling up to 16 boiler modules and hot water circuits

  • Easy access for servicing with quick to remove front cover hooks

  • Full spark ignitor enables servicing without the need to remove the whole burner

  • Low NOx performance (<40mg/kWh, European Class 6)

  • Non complicated design means the Purewell Variheat mk2 is easy to operate & maintain, saving on time and money

  • Highly efficient offering up to 96% gross seasonal efficiency, reducing carbon emissions and saving the end user money on fuel bills

  • Sits on same footprint as many traditional and atmospheric cast iron boilers reducing space concerns

  • Easy access to plant room as the Purewell Variheat mk2 fits through a standard doorway

  • Can be disassembled for plant rooms with difficult access

  • Tolerant of existing heating systems making the Purewell Variheat mk2 the perfect choice when replacing old atmospheric boilers

  • Operates in sealed and open vented heating systems (you can read about the differences of Sealed 'v' Open Vented heating systems here)

  • Suitable for use with LPG Air for installation in the Channel Islands

  • BIM objects available to assist in design and management

Ideal uses/applications

Optional extras

Reverse return header kit available for:

  • 2 boiler installation

  • 3 boiler installation

  • 4 boiler installation ( 2 x 2 boiler installation kit)

  • Flues available

  • Choose from a wide range of service contracts to help maintain optimum performance.

  • Book commissioning at the same time as placing your order for improved warranty terms.

  • Energy

    Units

    PV70c

    PV95c

    PV110c

    PV140c

    PV180c

    Building regulations - seasonal efficiency

    (%) gross

    95.3

    95.6

    95.8

    95.7

    94.6

    ErP efficiency rating (modules ≤ 70 kW only)

    A

    N/A

    N/A

    N/A

    N/A

    Boiler output (non-condensing) mean 70°C - max

    kW

    63.5

    86.3

    99.8

    134.4

    172.8

    Boiler output (non-condensing) mean 70°C - min

    kW

    21.2

    28.8

    33.3

    44.8

    50.3

    Boiler output (condensing) mean 40°C - max

    kW

    70

    95

    110

    140

    180

    Boiler output (condensing) mean 40°C - min

    kW

    23.3

    31.67

    36.37

    46.67

    53.0

    Gross boiler input - max

    kW

    72.2

    98.4

    115

    151.3

    194.6

    Gross boiler input - min

    kW

    24.1

    26.7

    38.3

    50.4

    56.6

    Net boiler input - max

    kW

    65

    88.6

    103.5

    136.3

    175.2

    Net boiler input - min

    kW

    21.7

    29.6

    34.5

    45.4

    51.0

  • Water

    Units

    PV70c

    PV95c

    PV110c

    PV140c

    PV180c

    Water content

    litres

    8

    8

    8

    11

    11

    System design flow rate @ 20°C ∆T rise

    l/s

    0.8

    1.1

    1.3

    1.7

    2.1

    Water side pressure loss @ 20°C ∆T rise

    mbar

    32

    52

    72

    134

    221

    System design flow rate @ 11°C ∆T rise

    l/s

    1.5

    2.1

    2.4

    3

    3.9

    Water side pressure loss @ 11°C ∆T rise

    mbar

    96

    176

    244

    442

    731

    Maximum water pressure

    bar g

    6

    6

    6

    6

    6

  • Gas

    Units

    PV70c

    PV95c

    PV110c

    PV140c

    PV180c

    Gas flow rate natural gas (G20) - max

    m3/hr

    6.9

    9.4

    10.9

    14.4

    18.5

    Nominal inlet pressure natural gas (G20) - max

    mbar

    20

    20

    20

    20

    20

    Maximum gas inlet pressure natural gas (G20)

    mbar

    25

    25

    25

    25

    25

  • Flue

    Units

    PV70c

    PV95c

    PV110c

    PV140c

    PV180c

    Flue Gas Flow Rate@ 15°C, 9.5% CO2

    m3/hr

    86

    117

    137

    180

    232

    Approx. flue gas temperature @ 50/30°C

    °C

    40

    40

    45

    50

    50

    Approx. flue gas temperature @ 80/60°C

    °C

    60

    60

    65

    70

    75

    Pressure at boiler flue spigot @full load

    Pa

    100

    100

    100

    100

    100

    Dry NOx emission*

    mg/kWh

    21.3

    31.1

    39.1

    32

    37.8

  • Connection

    Units

    PV70c

    PV95c

    PV110c

    PV140c

    PV180c

    Water flow/return connections

    inches

    R2”

    R2”

    R2”

    R2”

    R2”

    Gas inlet connection pipe thread size

    inches

    R1”

    R1”

    R1”

    R1”

    R1”

    Nominal flue diameter (I/D)

    mm

    150

    150

    150

    150

    150

  • Electrics

    Units

    PV70c

    PV95c

    PV110c

    PV140c

    PV180c

    Electrical supply

    230 V 1 Ph 50 Hz

    230 V 1 Ph 50 Hz

    230 V 1 Ph 50 Hz

    230 V 1 Ph 50 Hz

    230 V 1 Ph 50 Hz

    Power consumption @ max

    W

    94

    94

    94

    207

    207

    IEC power outlet power consumption @ max

    W

    460

    460

    460

    460

    460

    Start current and run current

    Amp

    0.54

    0.54

    0.54

    0.6

    0.6

    Approx shipping weight

    kg

    195

    195

    195

    250

    250

    Noise emission @1 m and @maximum boiler modulation

    Max dB (A)

    53

    53

    53

    65

    65

    CO2 (±0.25%) - max

    %

    9.5

    9.5

    9.5

    9.5

    9.5

    CO2 (±0.25%) - min

    %

    9.5

    9.5

    9.5

    8.5

    8.5

    *0% excess oxygen, dry air free, European Class 6

Frequently Asked Questions

Can the Purewell Variheat boiler run on an open vented system?

Yes. The Purewell Variheat boiler is able to operate on an open vented heating system.

We would advise compliance with minimum pressure requirements at boiler, reference guidance note INDG436 (Health and Safety Executive).

Open vent and cold feed pipes must be installed correctly and in compliance with BS6644. You can refer to the installer guide for detailed information on Open Vent and Cold Feed pipes.

However, Hamworthy recommends the use of sealed heating systems, where possible.

If you want to know the difference between a sealed system and open vented system, find out more here.

  • Can the Purewell Variheat boiler run on an open vented system?

    Yes. The Purewell Variheat boiler is able to operate on an open vented heating system.

    We would advise compliance with minimum pressure requirements at boiler, reference guidance note INDG436 (Health and Safety Executive).

    Open vent and cold feed pipes must be installed correctly and in compliance with BS6644. You can refer to the installer guide for detailed information on Open Vent and Cold Feed pipes.

    However, Hamworthy recommends the use of sealed heating systems, where possible.

    If you want to know the difference between a sealed system and open vented system, find out more here.

Partnerships

CIBSE Patron WhiteSoPHE Logo
BESA logo
ICOM

Hamworthy Heating 2025. All Rights Reserved

  • Youtube